Atatürk Üniversitesi Atatürk Üniversitesi
Ara
Yayınlara dön
Makale Tam Makale Uluslararası 2009

ANFIS-Based Compensation Algorithm for Current-Transformer Saturation Effects

Köksal Erentürk

IEEE TRANSACTIONS ON POWER DELIVERY Cilt 24 · Sayı 1 · ss. 195–201 · 01.01.2009
DOI ile aç

Özet

This paper proposes an efficient compensation algorithm based on an adaptive network-based fuzzy inference system capable of converting a sampled current waveform that is distorted by current-transformer (CT) saturation to a compensated current waveform. Quick response time, no cumulative estimation error, desired sample-by-sample output, no dependency of CT parameters/characteristics and secondary burdens, and simplicity are some attractive features of the proposed method. The accuracy and robustness of the introduced compensation algorithm are demonstrated through extensive test cases reflecting a wide range of variations in fault conditions and CT parameters. The proposed algorithm has also been implemented and tested on a digital signal processor board.

Anahtar kelimeler

IDENTIFICATION MODELS Adaptive network-based fuzzy inference system (ANFIS) compensation current transformers (CTs) saturable cores SECONDARY CURRENTS HYSTERESIS

Atıf için künye

Erentürk, K. (2009). ANFIS-Based Compensation Algorithm for Current-Transformer Saturation Effects. IEEE TRANSACTIONS ON POWER DELIVERY, 24(1), 195–201. https://doi.org/10.1109/tpwrd.2008.2005882

BibTeX
@article{erenturk2009-180701,
  author = {Erentürk, Köksal},
  title = {ANFIS-Based Compensation Algorithm for Current-Transformer Saturation Effects},
  journal = {IEEE TRANSACTIONS ON POWER DELIVERY},
  year = {2009},
  volume = {24},
  number = {1},
  pages = {195--201},
  issn = {0885-8977},
  doi = {10.1109/tpwrd.2008.2005882},
  url = {https://akademik.atauni.edu.tr/yayinlar/180701-anfis-based-compensation-algorithm-for-current-transformer-saturation-effects}
}